Contact the closest office: 1-800-358-5525

   Yokogawa Power Transducers 

Juxta AC Power Transducers --

 
  • 32 Different Models 
  • Industry Standard Inputs & Outputs 
  • Exceptional Long Term Stability 
  • 1 Year Warranty 
  • Input may be AC Volts, AC Amps, AC Watts, DC Volts, DC Milliamps, VARS, Phase Angle, Power Factor or Frequency 
  • Exceeds the IEEE472/ANSl C37.90.1-1989 Surge Withstand Capability 
  • Easily mounted


Model 2469 --

  • Accuracy: 0.5% of span; ±0.01 Power Factor; ±2° Phase Angle 
  • Sustained Input Overrange: Voltage --120% 

  • continuous, 150% for 5 seconds; Current --200% continuous, 1000% for 5 seconds 
  • Outputs: 0 to ±1 mADC into 10k(omega) max., 10VDC compliance; 4 to 20mADC into 750(omega) max., 15VDC compliance 
  • Output Adjust: zero ±1% min.; span ±2% min. 
  • Output Ripple: <0.3% of full scale peak to peak 
  • Response Time: <400 msec. 0-99% of full scale 
  • Power Supply Options: 24 or 48 VDC ±10% (UL Pending); 100-135VAC; 200-264VAC; 50/60 Hz; 5.0 VA max. 
  • Isolation: Input to Output -- 2500 VAC, 60Hz, 1 min. 
  • Input to Power -- 2500 VAC, 60Hz, 1 min. 
  • Input to Case -- 2500 VAC, 60Hz, 1 min. 
  • Power to Output -- 2000 VAC, 60Hz, 1 min. 
  • Power to Case -- 2000 VAC, 60Hz, 1 min. 
  • Output to Case -- 500 VAC, 60Hz, 1 min. 
  • UL Recognition

Model 2489

  • Accuracy: 0.2% of reading; ±0.01 Power Factor; ±1° Phase Angle 
  • Sustained Input Overrange: Voltage --120% 

  • continuous, 150% for 5 seconds; Current -- 200% continuous, 1000% for 5 seconds 
  • Outputs: 0 to ±1 mADC into 10k(omega) max., 10VDC compliance; 4 to 20mADC into 750(omega) max., 15VDC compliance 
  • Output Adjust: zero ±5% min.; span ±10% min. 
  • Output Ripple: <0.5% of full scale peak to peak 
  • Response Time: <400 msec. 0-99% of full scale 
  • Power Supply Options: 24 or 48VDC ±10% (UL Pending); 

  • 85-135VAC; 170-264VAC; 50/60 Hz; 5.0 VA max. 
  • Isolation: Input to Output -- 2500 VAC, 60Hz, 1 min. 
  • Input to Power -- 2500 VAC, 60Hz, 1 min. 
  • Input to Case -- 2500 VAC, 60Hz, 1 min. 
  • Power to Output -- 2000 VAC, 60Hz, 1 min. 
  • Power to Case -- 2000 VAC, 60Hz, 1 min. 
  • Output to Case -- 500 VAC, 60Hz, 1 min. 
  • UL Recognition 

Miniature Power Transducers 

Model 2370

  • Plastic case 
  • Surface mount 
  • Small footprint - 127 x 55 mm 
  • 0.5% of fullscale accuracy 
  • Available models: AC Volts, Amps, Frequency, Watts, VARs and Phase Angle 
    • - Single phase two wire 
    • - Single phase three wire 
    • - Three phase three wire 
    • - Three phase four wire (21&#142;2 and 3 elements) 
  • Isolation 
    • Input to output - 2600 VAC, 60 Hz, 1 min. 
    • Input to power - 2600 VAC, 60 Hz, 1 min. 
    • Input to case - 2600 VAC, 60 Hz, 1 min. 
    • Power to case - 2600 VAC, 60 Hz, 1 min. 
    • Output to case - 1000 VAC, 60 Hz, 1 min

About...  |  Table of Contents  | Manufacturer Index  | What's New

Send Inquiries to:

Copyright © 2007 Davis Inotek Instruments, LLC. All rights reserved.