Yokogawa Analog Panel Meters

Horizon Line AC Voltmeters/Ammeters, DC Voltmeters/Ammeters,
AC Motor Load Indicators, & AC Frequency Meters --
- Accuracy: All DC and AC iron-vane; ±2% of full-scale. AC rectifier
type; ±3% of full scale (with 60 Hz sine wave at 25°C). When
standard 60Hz iron vane ammeters are used at the extreme limits of 20 or
400 Hz, additional error (approx. 75%) may be experienced. Expanded-scale
voltmeters; ±.5% of full scale value
- All meters meet ANSI Specifications C-39.1
- Overload: Voltmeters (AC and DC) -50% momentary, 20% sustained. Ammeters
(AC and DC) momentary: 10 times the rated current for 10 consecutive intervals
of .5 second with a 1 minute interval between successive applications;
sustained: 20% for six hours
- Scale Data: 90 degree rotation
- Insulation Level: All meters (except 1 1/2"), 2600 VRMS Hi-pot, 1 1/2"-1500
VRMS Hi-pot
- Burden Data: AC ammeter-5 Amps, 0.5 va, max. 0.5 power-factor lagging.
AC voltmeter-unity power factor
- Response Time and Overshoot: Response time: 3 seconds (max.) for 2 1/2",
3 1/2",4 1/2" size for microammeters: 2 seconds (max.) for all other DC
ratings, and 2.5 Seconds (max.) for AC ratings. Maximum of 40% overshoot
- Custom ranges and scaling are available
Big Look AC Voltmeters/Ammeters, DC Voltmeters/Ammeters,
AC Motor Load Indicators, & AC Frequency Meters --
- Accuracy: All DC and AC iron-vane; ±2% of full-scale. AC rectifier
type; ±3% of full scale (with 60 Hz sine wave at 25°C). When
standard 60Hz iron vane ammeters are used at the extreme limits of 25 or
400 Hz, additional error (approx. 75%) may be experienced. Expanded-scale
voltmeters; ±5% of full scale value. All meters meet ANSI Specifications C-39.1
- Overload:
Voltmeters (AC and DC) - 50% momentary, 20% sustained. Ammeters (AC and
DC) momentary: 10 times the rated current for 10 consecutive intervals
of .5 second with a 1 minute interval between successive applications;
sustained: 20% for six hours
- Scale Data: 90 degree rotation
- Insulation Level: All meters (except 1 1/2"), 2600VRMS Hi-pot, 1 1/2"-1500VRMS
Hi-pot
- Burden Data: AC ammeter-5 Amps, 0.5 VA, Max. 0.5 power-factor lagging;
AC voltmeter - unity power factor
- Response Time and Overshoot: Response time: 3 seconds (max.) for 2 1/2",
3 1/2", 4 1/2" size for microammeters: 2 seconds (max.) for all other DC
ratings, and 2.5 seconds (max.) for AC ratings. Maximum of 40% overshoot
- Custom ranges and scaling are available
Type 185 Edgewise AC/DC Voltmeters/Ammeters --
- Completely shielded, dust-tight case
- No special calibration required for panel material
- Stack mounting of meters is possible with all sides of meter case flush
- Optional bezel/mounting bracket for 1-, 2-, or 3-unit stack (mounting
hardware not included)
- Zero regulator provided in rear of case
- Accuracy: DC meters ±2% of full scale. AC rectifier type ±3%
(60 Hz sine wave at 25°C)
- All meters meet ANSI Specification C-39.1
- Overload: Voltmeter: 50% momentary; 20% sustained Ammeter: 900% momentary.
20% sustained
- Scale Data: 53 degrees rotation. Length -1.785"
- Insulation Level: 1800 VRMS Hi-pot
- Response Time: 3 seconds (max.) for microammeters; 2 seconds (max.) for
all other DC ratings; and 2.5 seconds (max.) for AC ratings
- Overshoot: Maximum of 40%
Type 280 Thin Edgewise AC, DC Voltmeters/Ammeters
--
- Accuracy: ±2% of full scale, DC meters; ±3% with 60 Hz sine
wave at 25šC for AC rectifier type meters
- Overload: DC voltmeters -20% momentary and sustained; DC ammeters (momentary)
-10 times the rated current for 10 consecutive intervals of .5 second with
1 minute intervals between successive applications; DC ammeters (sustained)
- 20% for 6 hours
- Dielectric (Hi-pot): 1500 VRMS for 1 1/2" and 2 1/2" sizes; 2600 VRMs for
3 1/2" size
- Response Time: 3 seconds max for meters, 2 seconds (max.) formA, A, mV, & V meters
- Pointer Color: red standard
- Bezel and Mounting Hardware included with meter
- Overshoot: 25% (max.) for 1 1/2" size, 40% (max.) for 2 1/2" and 3 1/2" sizes
- Scale Data: All three sizes designed for 53 degrees deflection. Scale lengths
are: 1 1/2" size = 1.25", 2 1/2" size = 1.93", 3 1/2" size = 2.70". Note:
All scales have linear distributions. 10V, 15V, 30V Rectifier scales will
be non-linear
- All meters meet applicable sections of ANSI C39.1
- Custom ranges available
Elapsed Time Meters --
- New back-of-panel model
- 2 1/2" and 3 1/2" New Big Look models
- 2 1/2" and 3 1/2" round and square models
- UL recognition
- Conduit-case models available
- Optional 3 stud mounting available on 3 1/2" New Big Look type 240 meters
- Accuracy matches frequency control of power system
- Materials: clear Lexan case, Noryl frame, brass terminal studs, Lucite
front covers
-
Type 240 models available to operate on 120 or 208/240VAC, 50 or 60 Hz;
and 480VAC, 60 Hz
|