Ohio Semitronics Watt and Watthour Transducers
GW5 Series
 |
FEATURES
-
Accurate regardless of variations in voltage, current, power factor, or
load.
-
Available with 1, 1½, 2, 2½ or 3 element configurations.
Provides bi-directional operation.
-
Accuracy maintained over wide temperature range, calibration traceable
to NIST.
APPLICATIONS
-
Equipment monitoring for process control.
-
Integration into energy management systems, or a variety of sub-metering
applications.
-
Measurement using direct-connection, current transformers, and/or potential
transformers.
|
SPECIFICATIONS
INPUT:
-
VOLTAGE: Various - please CALL
-
CURRENT: Various - please CALL
-
FREQUENCY RANGE: 58 - 62 Hz.
-
Optional 50 Hz.: 48 - 52 Hz.
-
POWER FACTOR: Any
-
BURDEN:
-
Voltage: Less than 0.1VA per phase
-
Current: Less than 0.28VA per phase
-
Output amplifier: 2 Watts
-
OVERLOAD:
-
Voltage (cont.):
-
150V range: 175V
-
300V range: 350V
-
600V range: 600V
-
Current (cont.):
-
5A range: 2 times full-scale
-
10A range: 2 times full-scale
-
20A range: Full-scale
-
(transient):
-
All ranges
-
50A (10 sec./hr.)
-
250A (1 sec./hr.)
-
DIELECTRIC TEST (Input/Output/Case): 1800Vac (RMS)
-
SURGE: Withstands IEEE SWC test
-
INSTRUMENT POWER (STD.): 85 - 135Vac, 60 Hz, 7VA.
|
OUTPUT:
-
ACCURACY: ± 0.2% RDG.; ± 0.04% F.S.
-
(Includes combined effects of voltage, current, load and power factor.)
-
OUTPUT RIPPLE: Less than 0.5% F.S.
-
OUTPUT LOADING (OHMS):
-
0 - 1mA: 0 - 10K
-
0 - 10Vdc: 2K min.
-
4 - 20mA: 0 - 500
-
0 - 5Vdc: 2K min.
-
RESPONSE TIME (99%): Less than 200 milliseconds
-
FIELD ADJUSTABLE CAL.: ± 2% min.
-
COMPLIANCE VOLTAGE: 12Vdc min.
-
OPEN CIRCUIT VOLTAGE:
-
0 - 1mA, 0 - 10Vdc, 0 - 5Vdc outputs: ± 15Vdc
-
4 - 20mA output: + 30Vdc
-
TEMPERATURE EFFECT (-20o - 65ºC):
-
OPERATING HUMIDITY: 0 - 95% non-condensing
|
AGW Series Watt Transducers
 |
FEATURES
-
Accurate regardless of variations in voltage, current, power factor, or
load.
-
Available with 1, 2, 2 1/2, or 3 element configurations. Provides bi-directional
operation.
-
Accuracy maintained over wide temperature range, calibration traceable
to NIST.
APPLICATIONS
-
Equipment monitoring for process control.
-
Integration into energy management systems, or a variety of sub-metering
applications.
-
Measurement using direct-connection, current and/or potential transformers.
|
SPECIFICATIONS
INPUT:
-
VOLTAGE: Various- please CALL
-
CURRENT: 5A
-
FREQUENCY RANGE: 58 - 62 Hz.
-
POWER FACTOR: Any
-
BURDEN:
-
Voltage: Less than 0.1VA per phase
-
Current: Less than 0.25VA per phase
-
Output Amplifier: 2 Watts
-
OVERLOAD:
-
Voltage (cont.):
-
150V range: 175V
-
300V range: 350V
-
600V range: 600V
-
Current (cont.): 2 times full-scale
-
(transient):
-
50A (10 sec./hr.)
-
250A (1 sec./hr.)
-
DIELECTRIC TEST (Input/Output/Case):
-
(150V & 300V) 1800Vac
-
(600V) 2200Vac
-
SURGE: Withstands IEEE SWC test
|
OUTPUT:
-
ACCURACY: ± 0.2% RDG.; ± 0.04% F.S.
-
Includes combined effects of voltage, current, load and power factor.
-
OUTPUT RIPPLE: Less than 0.5% F.S.
-
OUTPUT LOADING (OHMS): 0 - 1mA: 0 - 10K
-
0 - 10Vdc: 2K min.
-
4 - 20mA: 0 - 500
-
RESPONSE TIME (99%): Less than 400 milliseconds
-
FIELD ADJUSTABLE CAL: ±2% min.
-
OPEN CIRCUIT VOLTAGE: ±1mA, ±10Vdc outputs: ±15Vdc
-
TEMPERATURE EFFECT(-20° - 60°C): ±0.005% per degree C
-
OPERATING HUMIDITY: 0 - 95% non-condensing
-
INSTRUMENT POWER (STD): 85 - 135Vac, 60 Hz, 7.5VA.
|
GH Series
 |
FEATURES
-
Accurate regardless of variations in voltage, current, power factor, or
load.
-
Available with 1, 2, 2 1/2, or 3 element configurations. Bi-directional
Watt and Watthour outputs available.
-
Accuracy maintained over wide temperature range, calibration traceable
to NIST.
APPLICATIONS
-
Equipment monitoring for process control.
-
Integration into energy management systems, or a variety of sub-metering
applications.
-
Measurement using direct-connection, current and/ or potential transformers.
|
SPECIFICATIONS
INPUT:
-
VOLTAGE: Various - please CALL
-
CURRENT: Various - please CALLFREQUENCY RANGE: 58 - 62 Hz.
-
Optional 50 Hz.: 48 - 52 Hz.
-
POWER FACTOR: Any
-
BURDEN:
-
Voltage: 0.1VA per phase
-
Current: 0.28VA per phase
-
OVERLOAD:
-
Voltage (cont.):
-
150V range: 175V
-
300V range: 350V
-
600V range: 600V
-
Current (cont.):
-
5A range: 2 times full-scale
-
10A range: 2 times full-scale
-
20A range: Full-scale
-
(transient):
-
All ranges
-
50A (10 sec./hr.)
-
250A (1 sec./hr.)
-
DIELECTRIC TEST (Input/Output/Case): 1800Vac (RMS)
-
SURGE: Withstands IEEE SWC test
|
OUTPUT:
-
ACCURACY: ± 0.2% RDG.; ± 0.05% F.S.
-
Includes combined effects of voltage, current, load and power factor.
-
WH RELAY: N/O SPST; 120Vac,0.5A rated,
-
contact closure period: 200 milliseconds
-
OPTION T: 5V TTL
-
OPTIONAL FORM C: Merc. wetted SPDT; 120Vac,
-
1.0A rated, contact closure period: 200 milliseconds
-
ANALOG OUTPUT RIPPLE: Less than 0.5% F.S.
-
OUTPUT LOADING (OHMS):
-
± 1mA: 0 - 10K, 4 - 20mA: 0 - 500
-
± 10Vdc: 2K min.
-
RESPONSE TIME (99%): Less than 400 milliseconds
-
FIELD ADJUSTABLE CAL.: ± 2% min.
-
COMPLIANCE VOLTAGE: 12Vdc min.
-
OPEN CIRCUIT VOLTAGE: ± 15Vdc
-
TEMPERATURE EFFECT (-20o - 60ºC):
-
OPERATING HUMIDITY: 0 - 95% non-condensing
-
INSTRUMENT POWER (STD.): 85 - 135Vac, 60 Hz., 7.5VA
|
AGH Series Watthour Transducers
 |
FEATURES
-
Accurate regardless of variations in voltage, current, power factor, or
load.
-
Available with 1, 2, 2 1/2, or 3 element configurations. Provides bi-directional
operation.
-
Accuracy maintained over wide temperature range, calibration traceable
to NIST.
APPLICATIONS
-
Equipment monitoring for process control.
-
Integration into energy management systems, or a variety of sub-metering
applications.
-
Measurement using direct-connection, current and/or potential transformers.
|
SPECIFICATIONS
INPUT:
-
VOLTAGE: Various- please
-
CALLCURRENT: 5A
-
FREQUENCY RANGE: 58 - 62 Hz.
-
POWER FACTOR: Any
-
BURDEN:
-
Voltage: Less than 0.1VA per phase
-
Current: Less than 0.25VA per phase
-
Output Amplifier: 2 Watts
-
OVERLOAD:
-
Voltage (cont.):
-
150V range: 175V
-
300V range: 350V
-
600V range: 600V
-
Current (cont.): 2 times full-scale
-
(transient):
-
50A (10 sec./hr.)
-
250A (1 sec./hr.)
-
DIELECTRIC TEST (Input/Output/Case):
-
(150V & 300V) 1800Vac
-
(600V) 2200Vac
-
SURGE: Withstands IEEE SWC test
|
OUTPUT:
-
ACCURACY: ± 0.2% RDG.; ± 0.04% F.S.
-
(Includes combined effects of voltage, current, load and power factor.)
-
WH RELAY: N/O SPST; 120Vac, 0.5A rated
-
Contact closure period: 200 milliseconds
-
CLOSURE CALIBRATION (STD.): 1 Watthour/closure
-
ANALOG OUTPUT RIPPLE: Less than 0.5% F.S.
-
ANALOG OUTPUT LOADING (OHMS): 0 - 1mA: 0 - 10K
-
0 - 10Vdc: 2K min.
-
4 - 20mA: 0 - 500
-
RESPONSE TIME (99%): Less than 400 milliseconds
-
TEMPERATURE EFFECT (-20o - 60ºC):
-
INSTRUMENT POWER: 90 - 135Vac, 60 Hz, 7.5VA
|
|