| Input Selection |
Typical Application |
Indicator |
DC Voltage or Current
(V, mV, A, mA)
Includes field configurable input ranges, curve fitting linearization
and square root extraction, wide ranging display with optimum filtering,
and conditioning to reduce susceptibility to transients and noisy operations
for accurate, stable readings |
DC Process signal monitoring and alarming, including ON/OFF
control, scaling and retransmission of process signal, two-wire transmitter
excitation, 4-20mA loop-powered indication. Flow control (V430) and batch
processing |
V108 (Indicating Alarm) 1/8 DIN
V116 (Indicating Alarm) 1/16 DIN
V132 (Indicating Alarm) 1/32 DIN
V408 (Universal/Modbus) 1/8 DIN
V430 (Flow, Rate, Totalizer) 1/8 DIN
V438 (Alarms, Retrans) 1/8 DIN
V560 (Loop Powered, IS)
V561 (Loop Powered, EP Housing)
V565 (Loop Powered, High Perf. IS) |
Thermocouple
(Types E, J, K, R, S, T)
Includes encapsulated cold-junction compensation (CJC) , and configurable
burnout detection. |
Temperature indication, montoring, alarming and retransmission
of temperature |
V108 (Indicating Alarm)1/8 DIN
V116 (Indicating Alarm) 1/16 DIN
V132 (Indicating Alarm) 1/32 DIN
V408 (Universal/Modbus) 1/8 DIN
V432 (Alarms, Retrans) 1/8 DIN |
RTD
(Type PT, NI, CU)
Includes mA DC excitation supply for accurate
stable measurement of 2 or 3-wire RTD resistance sensors |
Temperature indication, montoring, alarming
and retransmission of temperature |
V108 (Indicating Alarm)1/8
DIN
V116 (Indicating Alarm) 1/16 DIN
V132 (Indicating Alarm) 1/32 DIN
V408 (Universal/Modbus) 1/8 DIN
V432 (Alarms, Retrans) 1/8 DIN |
Strain-Gauge
( ±15mV to 200mV)
Includes 5 or 10V excitation, for bridges from
300 ohm to 10K ohm |
Pressure and load cell indication montoring,
alarming, ON/OFF control peak hold plus TARE... |
V408 (Universal/Modbus)
1/8 DIN
V434 (Alarms, Retrans) 1/8 DIN |
Potentiometer
(0-300 ohm to 0-10K ohm)
Includes 5 or 10V excitation supply for 3-wire
potentiometer or slidewires, to minimize circuitry at the sensor and provide
accurate stable measurement |
Tank level position and setpoint indication,
monitoring, alarming and ON/OFF control |
V408 (Universal/Modbus)
1/8 DIN
V438 (Alarms, Retrans) 1/8 DIN |
Frequency/Totalizer
(0-1Hz up to 0-30KHz)
Pulse or square wave, TTL, open collector or
contact closure 125mVpp to 120V amplitudes |
Flow, rate, speed, indication, totalization,
peak detect and alarming, including preset tracking for container fill
applications |
V437 (Alarms, Retrans)
1/8 DIN |
AC Current & Voltage
(0-5A, 0 to 50mV, up to 250V)
True RMS, high voltqage input or currnet inputs
with optional shunt resistor |
AC powered and load monitoring, alarming
and isolated retransmission of conditioned signal |
V436 (Alarms, Retrans)
1/8 DIN |
Temperature/Process Indicator
V108
|
Provides an Isolated Current Loop in Proportion
to an AC Input
-
Eliminates Ground Loops
- Easy Field Configurable Switch Selectable Input Ranges
- Wide Ranging Zero and Span Adjustability (80%)
- Protects Equipment with 600V Input-to- Output Isolation
-
Three Year Warranty
|
|
|
The VisiPak model V108 is a compact, 4 digit indicator
(with alarms) that fits 1/8 Din cutouts. It accepts temperature inputs
from J, K, T, L, N, R, S, B, C and Platinell II type thermocouples and
three-wire Platinum 100 Ohm (Pt100) RTDs. Process variables such as 4-20mA
or ranges within -9.99 to 80mV can also be measured. Other thermocouples
such as D and E types or custom curves can be configured at the factory.
Voltages ranges up to 0-10V can be measured with the optional (model SUB2-1V1)
adapter.
Three programmable setpoint alarms can be field configured
as rate of change, high or low, non-latching and high or low or new, latching
alarms. The new alarm indicates the situation when a latched alarm has
not been acknowledged and the measured value crosses the setpoint trip
level for the second time. Alarm hysterisis (deadband) can be configured
from 1 to 9999 process variable units. Each alarm has a programmable delay
up to 999.9 seconds.
The alarms can be linked to either of the relay outputs.
These alarms can be configured in combination (e.g. one or all three alarms
linked to one or both relays) and they will operate in fail-safe (e.g.
normally energized) or non-fail-safe modes. Additionally, the display can
be configured for password protection, limiting access to any or all functions.
An alarm blocking function is also configurable to prevent alarms from
tripping during a system’s initialization or start-up. Terminals are provided
to accept alarm acknowledgement (e.g. remote push button).
Thermocouple, three-wire RTD and mV inputs can be
directly input into the indicator. Current signals such as 4-20mA are input
using the 2.49W shunt resistor, which is included with the indicator and
mounting hardware. Other shunt resistors can be used to measure higher
current levels as long as the signal produced is within the -9.99mV to
80mV input range. Similarly, voltage inputs such as 0-10V can be measured
using the optional input adapter or voltage divider (model SUB2-1V1). The
four-digit display (9999) can be configured to match the input signal range
to the preferred engineering units. Offsets and two point slope adjustments
are fully programmable to compensate for sensor variances.
|
Miniature Temperature/Process
Indicator
V116,
V132
|
Provides a 4 Digit Display and Alarm Output
from RTD, Thermocouple or DC Inputs
-
Field Configurable Input for Thermocouple, RTD, mV, and 4-20mA Signals
- Three Field Configurable Alarm Setpoint with One or Two Alarm Outputs
-
Bright Green 4 Digit (9999) LED Display, Programmable for Engineering Units
-
Combination Alarm Functions, Alarm Blocking and Programmable Latching/Non-latching
- NEMA 4X Front Panel with Tactile Front Panel Configuration Buttons
-
Wide Ranging Power Supply: 85 to 264VAC or 20 to 29V DC or AC
-
Three Year Warranty
|
|
|
The VisiPak models V116 and V132 are compact, 4 digit
indicators (with alarms) that fit 1/16 and 1/32 Din cutouts, respectively.
They accept temperature inputs from J, K, T, L, N, R, S, C, B, and Platinell
II type thermocouples and two-wire Platinum 100 Ohm (Pt100) RTDs. Process
variables such as 4-20mA or ranges within -12 to 80mV can also be measured.
Other thermocouples such as D and E types or custom curves can be configured
at the factory. Voltages ranges up to 0-10V can be measured with the optional
(model SUB2-1V1) adapter.
Three programmable setpoint alarms can be field configured
as high or low, non-latching and high or low or new, latching alarms. The
new alarm indicates the situation when a latched alarm has not been acknowledged
and the measured value crosses the setpoint trip level for the second time.
Alarm hysterisis (deadband) can be configured from 1 to 9999 process variable
units.
The alarms can be linked to either the relay output
or the digital I/O terminals. The digital I/O terminals can be configured
to accept alarm acknowledgment input (e.g. remote push button). Or when
configured as an output, those terminals will provide a TTL signal or drive
an optional (model SUB2-1R7) relay. These alarm outputs can be configured
in combination (e.g. one or all three alarms linked to the relay) and will
operate in fail-safe (e.g. normally energized) or non-fail-safe modes.
Additionally, the display can be configured for password protection, limiting
access to any or all functions.An alarm blocking function is also configurable
to prevent alarms from tripping during a system’s initialization or start-up.
Thermocouple, two-wire RTD and mV inputs can be directly
input into the indicator. Current signals such as 4-20mA are input using
the 2.49W shunt resistor, which is included with the indicator and mounting
hardware. Other shunt resistors can be used to measure higher current levels
as long as the signal produced is within the -12mV to 80mV input range.
Similarly, voltage inputs such as 0-10V can be measured using the optional
input adapter or voltage divider (model SUB2-1V1). The four-digit display
(9999) can be configured to match the input signal range to the preferred
engineering units. Offsets and two point slope adjustments are fully programmable
to compensate for sensor variances.
|
Universal Temperature/Pressure/Process
Indicator
V408
|
Provides a 5 Digit Green or Red Display
and Alarm Outputs from RTD, Thermocouple, Strain-Gauge or DC Inputs
- Universal Field Configurable Input for Thermocouple, RTD, mV, bridge, 0-10V
and 4-20mA Signals
- Optimal modular Design Provides 3 Option Slots plus one Optional ModbusÒCommunication
Slot
- Option modules for 2nd Input, DC Retrans, Sensor Excitation, 3 Digital
Inputs and Outputs, and Relays
- Four Field Configurable Setpoints Support Combination Alarm Functions,
Rate of Change, Deviation Alarms, Alarm Blocking and Latching/Non-latching
-
NEMA 4 Front Panel with Plug-in From Front Design for Quick Replacement
(Low MTTR)
- Wide Ranging Power Supply: 85 to 264VAC or optional 20 to 29V DC or AC
-
Three Year Warranty
|
 |
|
The VisiPak model V408 is a 1/8 DIN, universal, 5
digit indicator with four alarms, two digital inputs and one SPDT relay
output. Available with a green or red display, it accepts temperature inputs
from J, K, T, L, N, R, S, B, C and Platinell II type thermocouples and
three-wire Platinum 100 Ohm (Pt100) RTDs. Process variables such as 4-20mA,
1-5V and 0-10V as well as strain gauge, bridge inputs can also be measured.
Other thermocouples or sensors such as D and E types or high accuracy 20
to 80 point custom linearization curves can be configured at the factory.
Square root extraction or eight-point curve linearization can be user defined
in the field. A second process input is available to accept remote setpoints
and compare signals such as the average, difference, or selecting minimum
or maximum readings.
|
Analog Input, Rate Indicator/Totalizer/Batch
Controller
V430
|
Provides a Digital Display of Rate or
Totalized Count from a DC Current or Voltage Input
- Field Configurable Input Accepts 4 to 20mA, 1 to 5V, 0 to 5V, or 0 to 10V
Signals
- 6 Digit Display for Counts up to +999999, Independent Scaling for Both
Rate and Total
-
Programmable Square Root, 11 Point Linearization and Peak Hold Functions
-
4 Visual Alarm Points with Front Panel LED Status Indication
- Optional 2 Relay Output and 4-20mA Transmitter Output
-
Isolated 24V Excitation Source
-
NEMA 4X Front Panel
|
|
|
The VisiPak model V430 is a programmable, analog
input LED indicator which displays either rate or the totalized count of
the rate. The time base of the rate can be set for seconds, minutes, hours
(e.g. pulses per second, gallons per minute, or barrels per day) and the
totalization factor can be set for conversion of rate units to totalization
units (e.g. gallons per minute rate converted to totalized barrels).
The VisiPak housing provides a NEMA 4X water tight
front panel that fits 1/8 DIN cutouts. Additionally, square root, peak
hold, low flow cut-off, square root and 11 point linearization functions
are also included.
The four visual setpoint alarms are standard and
annunciated via individual front panel LEDs. Two can be programmed to alarm
on rate limits and two can be programmed to alarm on a specific count or
total, complete with delays and offsets.
Two form C relays are available as optional outputs
for the first two setpoints; either two for rate or two for totalized count,
but not both. The rate alarms can be configured as high or low, failsafe
or non-failsafe. Each rate setpoint has a 100% adjustable deadband (or
reset points) which can be effectively used in on/off control applications
or as a latching alarm.
The totalized count alarms can be configured to trip
at an exact count or one can be programmed to trip at an off-set count
(e.g. set point #1 trips 10 counts before setpoint #2) for applications
where batch size varies. Additionally the Priority Batch Programming feature
allows quick access to the setpoints by holding the ENTER button down for
three seconds.
|
DC Input, Digital Indicator
V438
|
Provides a Digital Display of Process
Variables from DC Voltage and Current Inputs
- Field Configurable Input Accepts 4-20mA, 1-5V, 0-5V and 0-10V Signals
- 4 ½ Digit Display with Dummy Zero for 501 to +199990 Count Spans
-
4 Visual Alarm Points with Front Panel LED Status Indication
-
Optional 2 Relay Output and 4-20mA Transmitter Output
- Isolated 24V DC Excitation Source for 2-Wire Transmitter Inputs or the
Optional 4-20mA Output
- 11 Point Linearization and Square Root - Curve Fitting Functions
-
NEMA 4X Front Panel
|
 |
|
The VisiPak model V438 is a versatile, field configurable,
DC Current and Voltage input LED indicator which provides a NEMA 4X water
tight front panel that fits 1/8 DIN cutouts. The four visual setpoint alarms
are standard and annunciated via individual front panel LEDs.
Two form C relays are available as optional outputs
for the first two setpoints. They can be configured as high or low, failsafe
or non-failsafe. Each setpoint has a 100% adjustable deadband (or reset
points) which can be effectively used in on/off control applications or
as a latching alarms. An isolated 4-20mA transmitter output is also available
as an option, with or without the two relays.
The V438 accepts 4-20mA, 1-5V, 0-5V and 0-10V inputs
and displays any engineering scale required, between 501 and + 199990 counts
with a programmable decimal for the full-scale span. There is an isolated
24V excitation source to power a two-wire transmitter or transducer.
Field configuration of the input range, alarm function,
and analog transmitter output scaling is quick and easy since only one
button is required to toggle through the selections. The indicator is factory
calibrated to rated accuracy but can be checked and adjusted in the field
if necessary, using the same configuration button.
A second front panel button is used for acknowledgement
of alarms. This button can be pushed to unlatch or reset the optional output
relay. For remote acknowledgement, terminals are provide to allow wiring
of a switch to a different location.
To prevent tampering and ensure safety a lockout
jumper is used to limit access to the configuration button functions. When
the lockout mode is enabled, only alarm setpoints and output scaling functions
are displayed and they can not be altered without moving the lock jumper.
|
Temperature Input, Digital Indicator
V432
|
Provides a Digital Display of Temperature
from RTD and Thermocouple Inputs
- Field Configurable Input Accepts Pt100W RTD and J, K, T, E, R & S Type
t/c Sensors
- RTDs (0.00385 or 0.00392 curve) to 1° or 0.1°
- 4 Visual Alarm Points with Front Panel LED Status Indication
- Optional 2 Relay Output and 4-20mA Transmitter Output
- NEMA 4X Front Panel • Displays °F or °C
|
 |
|
The VisiPak model V432 is a versatile, field configurable,
RTD and Thermocouple input LED indicator which provides a NEMA 4X water
tight front panel that fits 1/8 DIN cutouts. The four visual setpoint alarms
are standard and annunciated via individual front panel LEDs.
Two form C relays are available as optional outputs
for the first two setpoints. They can be configured as high or low, failsafe
or non-failsafe. Each setpoint has a 100% adjustable deadband (or reset
points) which can be effectively used in on/off control applications or
as a latching alarm. An isolated 4-20mA transmitter output is also available
as an option, with or without the two relays.
The V432 accepts types J, K, T, E, R, and S thermocouples
and 100W Pt RTD (.00385 and .00392 alpha curves) and displays temperature
with 1 degree resolution (°F or °C). In addition, type T thermocouple
and the 100W Pt RTD may be diplayed at 0.1 degree resolution.
Field configuration of the input type, alarm function,
and analog transmitter output scaling is quick and easy since only one
button is required to toggle through the selections. The indicator is factory
calibrated to rated accuracy but can be checked and adjusted in the field
if necessary, using the same configuration button.
|
Frequency/Pulse Input, Rate Indicator/Totalizer/Batch
Controller
V437
|
Provides a Digital Display of Rate or
Totalized Count from a Frequency or Pulse Input
- Field Configurable Input Accepts Pulse, Open Colletor, Switch Closure,
TTL or Square Wave Signals
-
6 Digit Display for Counts up to +999999
- 4 Visual Alarm Points with Front Panel LED Status Indication
-
Optional 2 Relay Output and 4-20mA Transmitter Output
- Isolated 12V and 24V Excitation Source
- Programmable 11 Point Linearization and Peak Hold Functions
-
NEMA 4X Front Panel
|
 |
|
The VisiPak model V437 is a versatile, field configurable,
AC Current and Voltage input LED indicator which provides a NEMA 4X water
tight front panel that fits 1/8 DIN cutouts. The four visual setpoint alarms
are standard and annunciated via individual front panel LEDs.
Two form C relays are available as optional outputs
for the first two setpoints. They can be configured as high or low, failsafe
or non-failsafe. Each setpoint has a 100% adjustable deadband (or reset
points) which can be effectively used in on/off control applications or
as a latching alarms. An isolated 4-20mA transmitter output is also available
as an option, with or without the two relays.
The V437 accepts 50mV, 200mV, 2V, 20V, or 250VAC
inputs and displays any engineering scale required, between 501 and + 199990
counts for the full-scale span. Current inputs up to 5A can be measured
across a 0.1W shunt resistor (model C006) accessory. There is an isolated
24V excitation source to power the transmitter output.
Field configuration of the input range, alarm function,
and analog transmitter output scaling is quick and easy since only one
button is required to toggle through the selections. The indicator is factory
calibrated to rated accuracy but can be checked and adjusted in the field
if necessary, using the same configuration button.
A second front panel button is used for acknowledgement
of alarms. This button can be pushed to unlatch or reset the optional output
relay. For remote acknowledgement, terminals are provide to allow wiring
of a switch to a different location.
To prevent tampering and ensure safety a lockout
jumper is used to limit access to the configuration button functions. When
the lockout mode is enabled, only alarm setpoints and output scaling functions
are displayed and they can not be altered without moving the lock jumper.
|
TRUE RMS AC Input, Digital Indicator
V436
|
Provides a Digital Display of Process
Variables from AC Voltage Inputs
- Field Configurable Input Accepts 50mV, 200mV, 2V, 20V or 250V Signals
- 4 ½ Digit Display with Dummy Zero for 501 to +199990 Count Spans
- 4 Visual Alarm Points with Front Panel LED Status Indication
- Optional 2 Relay Output and 4-20mA Transmitter Output
- Isolated 24V DC Excitation Source for Transmitter Output or Transducers
-
Noise Filter and Peak Value Functions
-
NEMA 4X Front Panel
|
 |
|
The VisiPak model V436 is a versatile, field configurable,
AC Current and Voltage input LED indicator which provides a NEMA 4X water
tight front panel that fits 1/8 DIN cutouts. The four visual setpoint alarms
are standard and annunciated via individual front panel LEDs.
Two form C relays are available as optional outputs
for the first two setpoints. They can be configured as high or low, failsafe
or non-failsafe. Each setpoint has a 100% adjustable deadband (or reset
points) which can be effectively used in on/off control applications or
as a latching alarms. An isolated 4-20mA transmitter output is also available
as an option, with or without the two relays.
The V436 accepts 50mV, 200mV, 2V, 20V, or 250VAC
inputs and displays any engineering scale required, between 501 and + 199990
counts for the full-scale span. Current inputs up to 5A can be measured
across a 0.1W shunt resistor (model C006) accessory. There is an isolated
24V excitation source to power the transmitter output.
Field configuration of the input range, alarm function,
and analog transmitter output scaling is quick and easy since only one
button is required to toggle through the selections. The indicator is factory
calibrated to rated accuracy but can be checked and adjusted in the field
if necessary, using the same configuration button.
A second front panel button is used for acknowledgement
of alarms. This button can be pushed to unlatch or reset the optional output
relay. For remote acknowledgement, terminals are provide to allow wiring
of a switch to a different location.
To prevent tampering and ensure safety a lockout
jumper is used to limit access to the configuration button functions. When
the lockout mode is enabled, only alarm setpoints and output scaling functions
are displayed and they can not be altered without moving the lock jumper.
|